D-040 - 2” COMBINATION AIR VALVE “BARAK”
Description
The D-040 Combination Air Valve has the features of both an Air-release
valve and an Air/vacuum valve.The Air-release component of the D-040
was designed to automatically release to the atmosphere small pockets
of air as they accumulate at local high points along a pipeline when
the pipeline or piping system is full and operating under pressure. The
Air/vacuum component was designed to automatically discharge or admit
large volumes of air during the filling or draining of a pipeline or
piping system. This valve will open to relieve negative pressures whenever
water column separation occurs.
Main
Features
Working pressure range: 2": 3-250 psi. Testing pressure: 360
psi.
Maximum working temperature 203° f.
Light, simple and reliable structure.
Prevents premature closing:
- The valve discharges air at high velocity.
- The orifice of the Automatic continuous acting valve is larger than in
any other air release valve of it's kind, therefore it discharges air at
higher flow rates.
The size of the Automatic orifice makes its obstruction by debris
most unlikely. The valve design - Rolling Seal Mechanism: is less sensitive
to pressure differentials than a direct float seal. It accomplishes this
by having a comparably large orifice for a wide pressure range(up to 250
psi).
The body is made of high strength plastic, and all operating parts
are made of specially selected corrosion resistant materials.
Due to its light weight, the valve may be installed on plastic piping
systems, as well as other lightweight piping.
A threaded drainage outlet enables removal of excess fluids (1½").
Valve Selection
The D-040 air valve is available:
With 2" male NPT connections.
With a Vacuum Guarding, Out-only attachment, which only allows air discharge,
not allowing air intake.
With a Vacuum Breaking, In-only attachment, which only allows air intake,
not allowing air discharge.
With a Non-Slam, discharge-throttling attachment, which allows free air
intake, but throttles air discharge.
With Threaded Outlet.
Ordering:
Upon ordering, please specify: model,
size, working pressure, threads/flanges standard and type of liquid.
More information:
Data sheet